gas sensor, gas leakage alarm - HANKOOK GASKIKI
 
CompanyProduct CertificateInquiry
Technical Data
Relevant Laws And Regulations
 
Certificate
Inquiry
  


Relevant Laws And Regulations

 
ST ANDARDS OF MODEL APPROVAL AND INSPECTION TECHNOLOGY FOR

GAS LEAKAGE DETECTORS (KFI 0309)
KFI =Korea Fire Equipment Inspection Coporation)
 
Ministry of Home Affairs Notice No. 24
(1990.12.14 )
Ministry of Home Affairs Notice
No. 1993-18 (1993. 01.07 )
Ministry of Home Affairs Notice
No.1994-60
(1994.12.08 )
Ministry of Home Affairs Notice
No.1995-39
(1994.09.25 )
Ministry of Home Affairs Notice
No.1997-98
(1997.12.11 )
Ministry of Government Administration
and Home Affairs Notice
No. 1998-42
(1998.03.07 )
Ministry of Governmen tAdministration
and Home Affairs Notice
No.1999-44
(1999.08.03 )
 
Article 1 (Purpose)
This Standard shall specify the standards of model approval and inspection technology for gas leakage detectors regulated in article 50, clause 3 of Fire Service Law and article 36 of enforcement order of the same law.
 
Article 2 (Definitions)
The definitions of the terms used in this standard are as follows.
1. ¡°Alarm device¡± shall be a device intended to give a fire alarm for an outbreak of fire or a situation which fire is expected. Alarm device shall include automatic fire detection system, battery for fire alarm device, fire alarm system, current leakage alarm unit, and gas leakage detector.
 
2. ¡°Gas leakage detector¡± shall be a device intended to detect leakage of combustible gas or incompletely combusted gas and then notify people concerned or users. However, detectors without detection device or potable detectors for inspection or detector alarming by an interlocking device shall not be included (hereinafter called as detector)
 
3. ¡°Explosion-proof type¡± shall prevent the container from busting or prevent outside gases from igniting when an explosive gas is exploded inside the container.
 
4. ¡°Water-prooftype¡± shall have waterproof structure.
 
5. ¡°Detecting part¡± shall be a part of gas leakage detector (hereinafter called as Detector) that detects gas leakage, sends the gas leakage signal to transmitter or receiving part and makes sound for alarming.
 
6. ¡°Receiving part¡± shall be a device intended to receive gas leakage signals from detecting part of gas leakage detector, directly or via a transmitter, and then to notify the people concerned or the fire department.
 
7. ¡°Join alarming part¡± shall be an accessory of detector intended to receive a signal from receiving part of detector and make an alarm sound.
 
8. ¡° accessories¡± shall be an additionally attached device to detector to supply operation signal source to zone alarm unit and fans for gas ventilation.
 
9. ¡°Separate type¡± is a detector with separate receiving part and detecting part.
 
10. ¡°Self-contained type¡± is an detector with detecting part and receiving part in one box.
 
11. ¡°Transmitter¡± shall be a device intended to give signals from detector, manual fire alarm box (except M-type) or detecting part of a gas leakage detector to c.i.e (except M-type) or receiving part. Transmitter shall give control and leakage signals or amplify signals to a fire extinguishing system, a smoke control system, etc.
 
Article 3 (Classification of Gas Leakage Detector)
Detector shall be classified into self-contained detector and separate detector by structure. And self-contained detector shall be classified as a house-service device and separate detector shall be classified as a business and industrial device by purpose. In this case, a business device shall have 1 circuit and industrial device shall have 1 or more circuits.
 
Article 4 (General Structure)
General structure of detector shall conform to the following items.
1. Case of receiving part of detector and detecting part of separate type detector shall be made of incombustible or flame retardant materials. The case made of steel shall use over 1 mm thick steel plates and the case made of synthetic resin shall use 2.5 times plates as thick as steel (1.5 times for self-contained type or business device of separate type).
 
2. Case of receiving part of detector and detecting part of separate type detector made of synthetic resin (except zone window, instruction board, lid for cabinet, handle of switch, electric indicator, and indicating board of name) shall not be damaged at the temperature of over 80¡ÆC. They shall be made of self-fire extinguishing materials.
 
3. Gas leakage detector attached on a building shall be easily fixed with screw or nail, not with adhesive tapes.
 
4. Detector shall have indicating lamp to see the condition of power supply.
 
5. The parts which are possible to contain gas, like detecting part of self-contained detector and separate detector shall not make flame in the normal condition. Detecting part of industrial separate detector shall conform to one of the following explosion proof regulations.
A. Korean Industrial Standard
B. Standards from the gas related laws (law of high pressure gas safety administration, law of safety and business administration for liquefied petroleum gas, law of city gas business)
C. Standards from the industrial safety and health regulation
 
6. Detector shall be used only for detecting gas leakage and alarming. However, terminal for signal, power connectors for ventilation fan, GP type c.i.e, GP-type multiple c.i.e, GR-type c.i.e and GR-type multiple c.i.e, which operate control part in order to immediately stop liquefied petroleum gas and city gas (include liquefied natural gas. the same standards apply correspondingly to the following.) supply, shall be used for other purpose.
 
7. The part like power shut-off switch or alarming density adjustment part shall not be exposed outside.
 
8. A rated voltage circuit or a rated current circuit shall be installed to maintain constant voltage and not to be influenced by temperature change.
 
9. Detector shall be easy to operate, inspect, repair, and replace parts and have durability. They shall not make disturbing noise or interfering electric wave.
 
10. Detector shall not be functionally damaged by dust, moisture and insect etc.
 
11. The parts whose mechanical and electric functions are easily affected by corrosion
shall need rust-proof processing or anticorrosion processing by paint and plate. Copper alloys or the materials with corrosion resistance of more than the equivalent shall be used for the terminals, screws and washer affecting electric functions.
 
12. Wiring in equipment shall have a sufficient current carrying capacity, and its connections shall be firmly and accurately made.
 
13. Measures shall be taken incase of polarity to prevent misconnection.
 
14. Adhesion of parts shall not cause functional abnormalities and shall be firmly put together.
 
15. Measures shall be taken for current carrying parts except wires and a moving bolster to prevent misconnection.
 
16. Easy-accessible charging unit shall be protected.
 
17. Metal case of device with over 60 V rated voltage shall have earth terminals.
 
18. Detector shall be able to have stand-by power supply. Installation of stand-by power supply shall conform to following items.
A. Stand-by power supply shall not be used as main power source of detector.
B. Stand-by power supply shall have fuses to prevent damages from short circuits, etc.
C. Stand-by power supply shall be used only when main power source is stopped
D. A monitoring device shall be on the front side to watch the condition of stand-by power supply
E. Auto overcharge protection systems like auto-chargers and related electric devices
shall be installed. However, those systems shall not be installed if storage batteries are not damaged by over-charging.
F. When Stand-by power supplies are connected in parallel, measures shall be taken
to prevent reverse charge, etc.
G. When storage batteries are connected in series or in parallel, storage batteries shall
have evenness in capacity (current, voltage).
H. Stand-by power supply shall be cylindrical sealed nickel-cadmium storage battery or sealed lead-acid battery. Stand-by power supply for 1 line (including self-contained detector) shall be able to supply power and give an alarm for 10 min, after monitoring 20 min. Detector for 2 lines or more shall be able to supply power and give an alarm. for 10 min after monitoring of every connected circuits for 10 min.
 
19. (Delete 1995.9.25)
 
20. Protective measures shall be taken by heatproof boards or holes for those affected by heat generated from internal parts and etc.
 
Article 5 (Structure of Receiving Part of Separate Type Detector)
The structure of receiving part of separate detector shall conform to following items. However, detector for business shall not conform to clause 1, 5, 6 and 8.
1. A switch shall be installed inside to open and close both polarities of main power source simultaneously.
 
2. Protection devices such as fuses, breakers etc. shall be installed to both lines of main
power source, 1 line of stand-by power supply circuit (if stand-by power source is
installed) and circuits supplying power from receiving part to external load.
 
3. (Delete 1997.12.11)
 
4 .(Delete1997.12.11)
 
5. Voltmeter can be installed to monitor voltage on the front of main circuit and a power relay and reversion switch shall be installed to load part.
 
6. A switch shall be in installed to stop operation or sound of sound devices and used for its own purpose (except those for 1 circuit).
 
7. If manual return switch is used, a sound signaling device or a switch position warning lamp shall be installed.
 
8. A device monitoring gas density near detecting part, operation tester for gas leakage indication and earth continuity tester shall be installed on the front. However those with single connectable line or devices indicating power interruption of the detecting part to inform to sounding device cannot conform to this provision.
 
Article 6 (Functions of Receiving Part of Separate Type Detecting Part)
Receiving Part of separate detector shall conform to the following items. However, industrial devices cannot conform to item number 1, 2 and 4.
1. Gas leakage shall be indicated in case of receiving gas leakage signal from other line when gas leakage indication tester is operating.
 
2. Gas leakage shall be indicated, after receiving gas leakage signals from 2 lines at the same time.
 
3. Gas leakage shall be indicated in case of receiving gas leakage signal from other line when earth continuity tester is operating. However those with single connectable line or devices indicating power interruption of the detecting part to inform to sounding device cannot conform to this provision.
 
4. As soon as receiving the following signal, sound devices and fault indicating lamp shall be operated automatically.
A. In case of operation of fuse, _reaker and other protection device supplying power from detecting part, receiving part and transmitter, whose power is supplied from other transmitter, to external load
B. In case that power source of transmitter, whose power is not supplied by other transmitter, is blocked and in case of operating of protection device such as fuse and breaker of circuit supplying power from the transmitter to external load
 
5. The time from receiving gas leakage signal to indicating gas leakage shall be within 60 sec.
 
6. (Delete 1997.12.11)
 
7. In receiving signal according to the clause 14-a, 15-a of article 3 of Standards Model Approval and Inspection Technology for Transmitter, sound alarm or indicating lamp shall be operated automatically to notify mechanical problems.
 
Article 6 - 2 (Structure and function of Suction Type Detector)
¨ç The structure of suction type detector shall conform to the following items.
1. Devices indicating suction rate shall have structure to display the suction quantity per unit time being readable.
 
2. Suction pump shall have enough capacity and operate without abnormalities.
 
3. Air flow meter shall be easily read, and gas suction rate shall be indicated by suction quantity per minute.
 
4. Filtering devices attached in air flow meter to prevent dust suction, shall be installed in front of air flow meter and shall be easy to replace.
 
5. The gas suction and venting pipes shall be made of copper pipes with 4 mm ~ 6 mm inside diameter and connected firmly with the connector like screws. The material of copper pipes shall conform to KS D 530 1 (copper or copper alloys pipe without seams) or more than equivalent in strength and corrosion resistance.
 
6. The entrance of gas suction pipe shall be protected from strainer (sintered metal of bronze, etc).
 
7. Suction types shall have test valve for suction rate test.
 
8. Pipes of input terminal and output terminal of detecting part shall prevent outside gas from igniting by inside flame of pipe.
 
9. In case of the type which body and the diaphragm of pump can be separated, the body and the diaphragm of pump shall be fixed by metal band like stainless steel or by bolt.
 
¨è Functions of suction type detector shall conform to the following items.
1. Suction rate shall be 1.5L or more when it is tested at the exhaust pipe after stabilized for 30 minutes under the condition of article 10.
 
2. Suction type detectors shall be airtight from the front end of suction pipe to the back end of venting pipe.
 
3. Material of rubber shall conform to KS M 6518(physical test for vulcanized rubber) and have more than equivalent performance.
A. Tensile strength shall be 150 gravity kg per 1 cm1 or more. After being kept in the air of 70¡¾2¡ÆC for 96 hr, the reduction rate shall be 20 % or less.
B. Modulus of elongation shall be 400 % or more. After put for 96 hours in the air of 70¡¾2¡ÆC, the reduction rate shall be 20 % or less.
C. Solidity shall be 70¡Æ or less, after being kept for 24 hours at the temperature of (-20¡¾2 ) ¡ÆC. The change of solidity shall not over ¡¾10.
D. Permanent compressive. contraction ratio for rubbers shall be 50 % or less, after being kept in the air of 100¡¾1 ¡ÆC for 70 hr.
 
4. Diaphragm for suction type detectors shall have corrosion resistance and gas corrosion resistance.
 
Article 7 (Test Device)
Devices for test of function regulated in article 6 shall conform to the following items.
1. Test shall be conducted easily in front of receiving part.
 
2. Continuity test of external wiring and measurement of circuit resistance shall be conducted on each circuit through appropriate _ethods such as done by electric indicator etc.
 
3. Even in the case of short circuit or line disconnection, tests shall be continued except tests of current leakage or main sound device.
 
4. If stand-by power supply is installed, the device testing the stand-by power supply shall be needed. In this case of test, a switch which is automatic reversion type shall be installed at the direct current side of the rectifier. After changing to stand-by power supply by this switch and letting actual load current flow, the terminal voltage of the stand-by power supply shall be measured.
 
Article 8 (Structure and Function of Parts)
In case that the following parts are required to be used for current leakage alarm units, they shall conform to the following items or more than the equivalent.
1. Switches
A. Switches shall be easy to use. Their resting points shall be clear and appropriate.
B. Switches shall not be damaged by the 10,000 times repetition test (5,000 times test for power switches). The current twice as high as the maximum operating current shall flow through the resistance load at the maximum operating voltage of each contact point.
C. Contact point shall withstand the maximum operating current and have corrosion resistance.
D. In case of switches which are blocked in the state of being laid down (mercury type switch, etc.), special devices shall be needed to prompt returning the switch to normal position.
 
2. Indicating lamps.
A. Light bulb shall have no breaking of wire, luminous flux change, graphiting, current reduction, etc. at the 130 % operating AC voltage for 20 hours.
B. Sockets shall firmly connect with light bulb, and light bulbs shall be easy to replace.
C. At least two light bulbs shall be connected in parallel except discharging lamp or light emitting diode.
D. Appropriate covers shall protect light bulbs, except light emitting diodes.
E. Indicating lamps intended to display a presence of current leakage (hereinafter called as current leakage lamp) and those to display location of zone which gas is leaked (hereinafter called as zone lamp shall be yellow in ) condition.
However, zone lamps of receiving part which current leakage lamp is installed or those with c.i.e shall not be yellow.
F. Indicating lamps shall be clearly identified at the distance of 3 m away from the front in ambient brightness of 3001x.
 
3. Electronic relays
A. Contact point shall be made of G. S. alloy, or materials of better quality.
B. Electronic relays shall be firmly attached not to be affected by self load and shall have dust proof covers to protect contact point and moving parts (except sealed electronic relay).
C. Electronic relays shall have no functional or structural critical abnormalities when subjected to the maximum operating current and voltage via resistance load.
D. Contact points shall be used as follows.
(1) Contact points for zone sound signaling device or zone indicating equipment shall not be used for other purposes (except those connected with auxiliary relays)
(2) Power shall not directly and concurrently supply to an internal load and an external load through one contact point.
 
4. Electric indicators shall conform to KS C 1303 (Electric Indicator) and voltmeters shall have full-scale ranges between 140 % and 200 % of rated voltages of circuits in which they are used.
 
5. Fuses
A. Fuse shall be with KS or electric mark for the approved product conforming to the requirements of KSC 8101 (Common Regulations of Wiring Fuses) or KSC 6039 (Shell Type Fuses for Electric Devices).
B. Fuses shall be easy for inspection and replacement.
C. Fuses shall be adhered not to be loose fitting.
 
6. Sound devices (including a zone alarming part on a gas leakage detector)
A. Sound devices shall produce sound at an 80 % rated operating voltage.
B. Sound pressure of a main sound device shall be 90 dB or more at an operating voltage at distance of 1 m from the front center of the equipment containing the sound device when it is tested in an anechoic room. (70 dB or more those for business among self-contained type and separate type) However_ those of system failure indicating equipments shall be 60 dB or more.
C. When conducting the test to ring for 8 hr continuously at the operating voltage or to ring for 3 min and 20 sec and pause for 6 min and 40 sec at the rated voltage for a total of 20 hr, there shall be no abnormalities in structure or function.
D. The insulation endurance between charring unit and discharging shall be to withstand for 1 min, A.C of effective of 500 V close to sinusoidal wave of 60 Hz (1000 V for rated voltage between 60 V and 150 V, and 1000 V plus rated voltage multiplied by 2 for rated voltage over 150 V).
E. The insulation resistance between charring unit and discharging unit shall be 20 Mil or more, when measured with a DC 500 V insulating tester.
 
7. Transformers
A. Transformers shall conform to KS C 6308 (SmaH Power Transformer for Electric Devices) or have better quality.
B. The primary rated voltage shall be 300 V or less and the case industrial transformer shall have an earth terminal.
C. Transformers shall withstand the maximum continuous operating current.
 
8. Stand-by power supply
A. Stand-by power supply shall not be used as main power source of detector.
B. Lead wires shall be appropriately colored for identification.
C. (Delete 1997.12.11.)
D. (Delete1997.12.11.)
E. (Delete1997.12.11.)
F. (Delete1997.12.11.)
G. (Delete1997.12.11.)
H. Electric charging and discharging tests for cylindrical nickel-cadmium storage battery shall be conducted based on the fully discharged state. In this case full discharge is to discharge at 0.6 V or less per cell. And each lead storage battery shall be charged with 0.1 C current to fully charged state and left alone for 1 hr, and then discharged with 0.05 C current to the final discharge voltage.
I. To conduct charging and discharging tests for cylindrical nickel-cadmium storage battery at room temperature, the fuHy discharged secondary shall be charged with rated voltage and current of 1/20 C at room temperature for 96 hr, and sealed lead-acid battery shall be discharged to discharge final discharge voltage and charged again with 0.1 C current for 48 hr. Then nickel-c_dmium storage batteries and sealed lead-acid batteries shall be able to be discharged with 1 C current for 48 min and 45 min or more, respectively.
J. To conduct high and low temperature exposure test for cylindrical nickel-cadmium storage battery, charge fully discharged cylindrical nickel-cadmium storage battery with current of 1/20 C and with the ambient temperature at (-10¡¾2) ¡ÆC and (50¡¾2) ¡ÆC for 96 hr and discharge it at 1 C. After repeating this cycle three times, duration for reaching final discharge voltage (Rated volume /1.414 V) shall be more than 20 min and there shall be neither bulging in appearance nor leaking liquid.
K. The sealed lead-acid batteries shall be completely charged with O. i C current for 48 hours and then, discharged with 0.05 C current for 1 hour. Thereafter the batteries shall be able to maintain 95 % rated volume after more than 30 min.
L. In case that stand-by power source is charged in reverse with current 1/5 C 1 C, safeguards shall operate within 5 min and there shall be neither bulging in appearance nor leaking liquid.
 
9. Semi-conductors shall have moisture proof processing and anticorrosion processing and withstand the maximum operating voltage and maximum operating current and shall have water or corrosion resistance.
 
10. The wiring connecting detecting part and receiving part (if there is a transmitter, the transmitter shall be included) shall have sufficient capacity not to prevent signal transmission.
 
Article 9 (Accessories)
¨ç Accessories shall not interrupt the functions of detector.
¨è Accessories of detector shall not give operating signal directly to breaking part. However, separate detector for industrial use shall not conform to this provision.
 
Article 10 (Test Environment)
Tests for detector shall be conducted at a room temperature in the range between 5 ¡ÆC and 35 ¡ÆC and at a relative humidity between 45 % and 85 % except specially regulated test.
 
Article 11 (Reception Indication)
Detector shall have proper reception indication and conform to the following items.
1. When detectors receive gas leakage signal they shall automatically indicate gas leakage with yellow leakage lamp or main sound device and concurrently indicate the zone of gas leakage with the zone lamp. However, self-contained detector or 1 circuit device shall not have the leakage lamp and zone lamp, etc.
 
2. The indication of clause 1 shall be stopped by manual return switch. However, industrial detector of self-contained detector and separate detector shall, not have manual return switch.
 
Detecting gas Test gas Operational test density (%) Non-operational test density (%)
Liquefied petroleum gas Isobutane (or butane, and so forth in this standard) 0.45120 0.05
Liquefied natural gas hydrogen 1.00 0.04
methane 1.25 0.05
Isobutane Isobutane 0.45 0.05
Methane Methane 1.25 1.00
Hydrogen Hydrogen 0.05 0.04
 
Article 12 (Maximum Load)
Detector shall have capacity to withstand the bigger one between load when all circuits are working and ordinary load continuously.
 
Article 13 (Ambient Temperature Test)
Receiving part of separate type detector shall have no functional abnormalities at the ambient temperature of 0¡ÆC ~ 40¡ÆC.
 
Article 14 (Repetition test)
Receiving part of separate type detector shall have no functional or structural abnormality, after 10,000 times gas leakage indicating operation at a rated voltage.
 
Article 15 (Transient Test)
Separate type detectors with current shall have no functional abnormalities when subjected to the following tests for 15 sec.
1. A test with a voltage of 500 V with an internal resistance of 50 Q at a pulse of 1 ms and at a repeated cycle of 100 Hz.
2. A test with a voltage of 500 V with an internal resistance of 50 Q at a pulse of 0.1 ms and at a repeated cycle of 100 Hz
 
Article 16 (Alarming Density Test)
¨ç After flowing electric current by over 1 hours for stabilization, detectors for combustible gas shall be tested by type of gas. Detectors shall give alarm sound in operational test within 20 sec (however, electrical delay type detector shall make alarm sound within 20_60 sec in operational test density) while they shall not give alarm sound in non-operational test density within 5 min.
 
Detecting gas Test gas Operational test density (%) Non-operational testdensity
First Second (0/0)
Incompletely Carbon    
0.025 0.055 0.005
combusted gas monoxide    
 
Remark: If the liquefied natural gas is detecting gas, test gas of gas leakage detector shall be hydrogen or methane.
 
¨è Tested by following table, an detector for the incompletely-combusted gas shall make alarm sound within 5 min at the first operational test density and within 1 min at the second operational test density after flowing electric current by over 1 hours for stabilization. The detector shall not make alarm sound in the non-operational test density for 5 min.
 
Article 17 (Long Term Performance Test)
Detector shall pass the alarming density test of article 16 and various gas test of article 19, after being charged with electriCity for 60 days and then not charged with electricity for another 60 days.
 
Article 18 (Voltage Variation Test)
Detectors shall pass alarming density tests of article 16 with the voltage fluctuation within rated voltage ¡¾ 10 %.
 
Article 19 (Various Gas Test)
Detectors shall not make sound during the following tests taken after flowing electric current by over 1 hour for stabilization. However, detectors for incompletely-combusted gas shall be only take a test of the clause 1.
1. The test of putting detector into 0.1 % ethanol gas for 5 min
2. The test of putting detector into the smoke of density regulated in article 19 of the standards of model approval and inspection technology for detector for 5 min (the operation test of optical detector 2 class)
 
Article 20 (Vibration Test)
Detectors (in case of separate type detector, it means detecting part as same as in article 21, article 23, article 25 and Article 26) shall have no functional abnormalities when vibrated at 4 mm peak-to-peak, in arbitrary direction 1,000 times per minute for 60 min.
 
Test gas A(%) B(%)
Methane 2.5 6.5~7.5
Hydrogen 2.0 19~23
Isobutane 0.9 2.5~3.3
 
Article 21 (Temperature Test)
Detectors (in the separate detector, it means detecting part) shall have no functional abnormalities in the following tests.
1. Detectors shall pass the test of article 16 after putting into the thermostat of -20¡¾2 ¡ÆC for 1 hour and then that of 40¡¾2 ¡ÆC for 1 hour.
2. Suction type detectors shall pass the test of Article 16 after three times putting into
the thermostat of -20¡¾2 ¡ÆC for 24 hours and then that of 40¡¾2 ¡ÆC for 24 hours. Before having test of article 16 it shall be stabilized for 1 hour.
 
Article 22 (Humidity Test)
Detectors shall have no functional abnormalities when they take alarming density test according to article 16 after being k_ept at the temperature of 35 ¡ÆC ~ 40¡ÆC and relative humidity over 85 % for 1 hour.
 
Article 23 (Explosion Proof Performance Test)
¨ç Detection devices for detecting gas leakage shall use STD 316 or more than the
equivalent 100-mesh nets of stainless steel wire. The holes (through which gas
flows) of the net shall not be widen or changed in shape. Detection devices of separate type detector shall be protected with strainers (sintered metal of bronze).
¨è The detector shall make sound for 7 hours at the test gas density of A, and then charged with electricity for 1 hour at the test gas density of B. (The power source shall be stopped twice for 1 sec) The detectors (except detectors conforming to article 4-5 of explosion proof structure) shall conform to the following items. The primary test gas shall be isobutane gas. However methane or hydrogen can be used according to the detecting gas type.
 
Test gas A(%) B(%)
Methane 2.5 6.5~7.5
Hydrogen 2.0 19~23
Isobutane 0.9 2.5~3.3
 
1. Detectors shall make alarm sound continuously for the while charged with electricity.
2. During the test, ambient gas of detectors shall not be exploded.
3. After the test, if the gas in the test box is ventilated, alarm sound shall stop. If it has structure which alarm sound is ringing continuously, the switch for return or sound device shall be used to stop the alarm manually.
 
Article 24 (Volume Test)
¨ç Sound pressure of a main sound device shall be 90 dB or more at an operating voltage at distance of 1 m from the front center of the equipment containing the sound device in an anechoic room (70 dB for business of self-contained type or separate type). However, those of system failure indicating equipments shall be 60 dB or more.
¨è There shall be no alarming sound when supplying power to detector, and no operating sound at distance of 1 m from the front center of the equipment containing the sound device.
 
Article 25 (Dust Test)
Detectors shall not be damaged when subjected to the alarming density test of article 16, charged with electricity, just after the dust test of Standards of Model Approval and Inspection Technology for Detector (KOFEIS 0301) article 31.
 
Article 26 (Impact Test)
Detectors (except suction type detectors) shall not be damaged when they take alarming density test according to article 16, immediately after more than two sides of an detector are once falling down from the height of 50 cm toward a 3 cm-thick wood board, charged with electricity, on the concrete floor.
 
Article 27 (Insulation Resistance Test)
¨ç Insulation resistance between each insulated charging unit and the case of detector
shall be 5 MQ(between AC input terminal and case shall be 20 MQ) or more when
measured with a DC 500 V insulating ohmmeter. However, insulation resistance of the detector which has more than 10 lines connected to transmitters (except insulation resistance between the AC input terminal and the case) shall be over 50 MQ per line.
¨è Insulation resistance between insulated cables shall be 20 MQ or more when
measured with a DC 500 V insulation ohlnmeter.
 
Article 28 (Insulation Endurance Test)
According to the article 27, insulation endurance of the aforementioned test part shall be to withstand for 1 min, AC of effective of 500 V close to sinusoidal wave of 60 Hz (1000 V for rated voltage between 60 V and 150 V, and 1000 V plus rated voltage multiplied by 2 for rated voltage over 150 V).
 
Article 29 (Water proof Test)
Water-proof type transmitters shall not store water inside and shall not damaged any parts or functions when transmitters on normal position are exposed in clean water falling at the angle of (45¡¾2)¡Æ degrees from the upper front side at the speed of 3 mm/min for one hour.
 
Article 29 - 2 (Electromagnetic Injury Test)
Detectors shall not have fault alarm, gas leakage false alarm or other abnormality during or after the test of following electromagnetic injury test in charged with electricity.
1. A test of radiating frequency band of radioactive materials 30 MHz, 50 MHz, 75 MHz, 144 MHz, 150 MHz, 460 MHz, 470 MHz, 850 MHz, 900 MHz, and 1000 MHz on detectors with the spreading strength of 10 V per meter for 1 min.
2. A test of radiating frequency between 30 Mhz and 1000 MHz, with the spreading
strength of 10 V per meter continuously to detectors from 1 m apart.
 
Article 30 (Marking and Accessories)
¨ç Separate type shall contain the following items in an easily recognizable area not to be erased easily.
1. Receiving part
A. Type and model
B. Model approval number
C. Manufacturing date, manufacturing number
D. Manufacturer_ name or commercial name (when the manufacturer and the seller (importer) are different, separately mark them.)
E. Treatment guide and handling cautions
F. Rated voltage and current of main power source
G. Number of connectable lines, maximum number of transmitter, the model approval number of connectable transmitter and the detecting part number
H. Type, rated volume, rated voltage and cautions of storage batteries if stand-by supply is installed
I. Standard delay time for delay types
2. Detecting part
A. Detecting gas and operating temperature
B. Operating place or purpose
C. Type of detection device (in case of explosion proof structure, separate marking of the explosion-prooftype and explosion proof grade)
D. Model approval number of clause 1-b, detecting part number
3. Terminal mark on terminal plate
4. Separate markings of water-prooftype
5. Separate markings of open and close near control handling method, etc.
6. Rated current near the fuses and fuse holders
7. Guidelines for Installation and treatment.
8. Separate markings of explosion-proof type? and explosion proof grade
¨è Self-contained type shall be indelibly marked with the items of clause 1-a, f, and i and clause 2-a and c, clause 3, and clause 7 on easily visible parts.
¨é Detector shall have the following accessories.
1. Preparatory light bulb (incandescent lamps only)
2. Preparatory fuse (excluding self-contained type)
¨ê The front side of detectors shall be marked with the phrase of as leakage detector? and the name of detecting gas. Also, the details about warranty (period, contents, A/S, self-inspection stamp, etc.) shall be indelibly marked on wraps, or handling manual or easily visible parts.
 
Article 31 (Detailed Regulations)
The detailed regulations for the enforcement of this standard shall be determined by the Minister of the Ministry of Government Administration and Home Affairs.
 
ADDITIONAL CLAUSE (1990.12.14.)
 
Article 1 (Date of Enforcement)
This standard shall be effective as from the day notified.
 
Article 2 (General Interim Measures of Lapse Concerning Model Approval and Model Modification Approval)
As for the approved fire protection machinery and objects in the model approval or model modification approval based on the previous regulations at the time of enforcement of this standard and those not suitable for this standard, they can apply for the model approval or model modification approval based on this standard within 6 months as of the date of enforcement of this standard and after 6 months, the model approval and model modification .. approval based on the previous standard shall be regarded as cancelled.
 
Article 3 (General Interim Measures of Lapse Concerning Individual Inspection)
As for the approved fire protection machinery and objects in the model approval or model modification approval based on the previous regulations at the time of enforcement of this standard, they can apply for individual inspection based on the previous regulations within 6 months as of the enforcement of this standard. However, as for those applied for individual inspection within that time period and rejected fire protection machinery and objects, they can apply for inspection again within 1 month as of the date receiving the notice of rejection regardless of reasons.
 
ADDITIONAL CLAUSE (1993.1.7.)
 
This standard shall be effective as from the day notified. However, article 30, clause 4 shall be effective as from April 1, 1993.
 
ADDITIONAL CLAUSE (1994.12.8.)
 
Article 1 (Date of Enforcement)
This standard shall be effective as from the day notified.
 
Article 2 (General Interim Measures for Model Approval andModelModificationl/pproval)
As for the approved fire protection machinery and objects in the model approval or model modification approval based on the previous regulations at the time of enforcement of this standard and those not suitable for this standard, they can apply for the model approval or model modification approval based on this standard within 6 months as of the date of enforcement of this standard and after 6 months, the model approval and model modification approval based on the previous standard shall be regarded as cancelled.
 
Article 3 (General Interim Measures for Individual Inspection)
As for the approved fire protection machinery and objects in the model approval or model _ modification approval based on the previous regulations at the time of enforcement of this standard, they can apply for individual inspection based on the previous regulations within 6 months as of the enforcement of this standard. However, as for those applied for individual inspection within that time period and rejected fire protection machinery and objects, they can apply for inspection again within 1 month as of the date receiving the notice of rejection regardless of reasons.
 
ADDITIONAL CLAUSE (1995.9.25.)
 
 
Article 1 (Date of Enforcement)
This standard shall be effective as trom the day notified.
 
Article 2 (General InterimMeasuresofModelApprovalandmodelModificationApproval)
The gas leakage detector, not conforming to this standard in spite of receiving the model approval or model modification approval according to the previous standard, shall apply for a model approval or model modification inspection until March 20, 1996. However, the model approval or model modification approval shall be regarded as not valid if the term passes.
 
Article 3 (General Interim Measures of Lapse Concerning Individual Inspection)
The fire extinguishing equipment, receiving model approval or model modification approval according to the previous standard, shall apply for an individual inspection until March 20, 1996 according to the previous standard. The disqualified extinguishing equipment (except rejected fire protection machinery and equipment because of incomplete manufacturing), shall be reapply for an individual inspection on within 1 month from a receipt date of the notice of disqualification limited to I time, regardless of application period.
 
ADDITIONAL CLAUSE (1997.12.11.)
 
Article 1 (Date of Enforcement)
This standard shall be effective as from the day notified.
 
Article 2 (General Interim Measures for Model Approval and Model Modification Approval)
The gas leakage detector, not conforming to this standard in spite of receiving the model approval or model modification approval according to article 17 of the previous standard, shall apply for a model approval or model modification inspection until March 7, 1997. However, the model approval or model modification approval shall be regarded as not valid if the term passes.
 
Article 3 (General Interim Measures of for Individual Inspection)
The fire extinguishing equipment, receiving model approval or model modification approval according to the previous standard, shall apply for an individual inspection until March 7, 1997 according to the previous standard. The disqualified extinguishing equipment shall be reapply for an individual inspection on within 1 month from a receipt date of the notice of disqualification, regardless of application period.
 
ADDITIONAL CLAUSE (1998.3.7.)
 
This standard shall be effective as from March 8, 1998.
 
ADDITIONAL CLAUSE (1999.8.3.)
 
Article 1 (Date of Enforcement)
This standard shall be effective as from 10 days after the date of Notice. However, article 2, clause 2, article 16, clause 2 and related items in article 19 (gas leakage detector for incomplete combustion gas) shall be effective as from 3 months after the day notified.
 
Article 2 (General Interim Measures for Before Product Inspection)
Gas leakage detectors having model approval under the previous standard, are required to apply for before product inspection under the standard within 3 months from the date of enforcement and after 3 months from the date of enforcement the product intend to apply for before product inspection shall conform this standards.
 
 
[ HANKOOK GASKIKI] [gas sensor] [gas leakage alarm] [residential gas leakage alarm] [industrial gas leakage alarm] [gas shutoff device] [Korea] [sitemap]